Reed level sensor: Defining the measuring range flexibly

A float-based level sensor with a reed chain is really a widely used and comparatively economical solution for continuous level measurement in vessels. Users can define its measuring range flexibly inside a given range. This article describes what should be taken into account.
With a reed-chain level sensor, the guide tube contains a defined amount of reed contacts, with respect to the measuring range. They are combined to create a measuring chain. The contacts respond to the magnetic field of the float, which moves within the guide tube good liquid level.
Accuracy depends on the distance between the contacts
The accuracy of this energy-free level monitoring depends, in turn, on the distance between your individual contacts: small it is, the more accurate the measurement. Each level sensor in WIKA?s RLT series, for instance, enables measuring ranges with contact distances between 3 and 24 mm. However, a reed chain cannot be stretched across the entire length of the guide tube. This is because there are ?dead bands? at both ends of the tube, i.e. sections that the float will not detect because of design constraints (see graphic).
The graph shows how the maximum possible measuring range (M) having an air-handling series level sensor is defined: Guide tube length (L) minus dead band (T) and 100 % mark (X).
Maximum measuring range isn’t a must
The measuring selection of an even sensor therefore lies between your two dead bands specified in the data sheet. In this range, it usually is freely defined. However, it is by no means necessary to utilise the utmost possible measuring range in all applications. The exact adaptation of the amount of contacts to the measuring task also has an economic advantage: The reed chain is probably the most expensive components in a level sensor.
Example ? Dry run monitoring
For dry run monitoring within an oil tank of a compressor, for example, only the lower part of the guide tube is necessary for the measurement. In this case, the upper measuring point of the application form (100 % mark) is defined correspondingly low. It marks the distance to the sealing face of the procedure connection. The measuring range is thus defined by the next equation:
Measuring range length M = guide tube length L ? dead band T ? ไดอะแฟรม , the measuring range for detecting a maximum level is determined beginning with the sealing face. In cases like this, the guide tube can be adapted to the length of the measuring range.
Note
Further information on the RLT series level sensors are available on the WIKA website. For those who have any questions, your contact will gladly assist you to.
Also read our articles
Level sensors ? the agony of preference
What do dead bands mean with a float switch?
There are also out more about float-based level measurement using a reed chain in the following video: